This research was sponsored by ASHRAE Technical Committee (TC) 4.3. The purpose of this Research Project is to provide a simple, yet accurate procedure for calculating the minimum distance required between the outlet of an exhaust system and the outdoor air intake to a ventilation system to avoid re-entrainment of exhaust gases. The new procedure addresses the technical deficiencies in the simplified equations and tables that are currently in Standard 62.1-2013 Ventilation for Acceptable Indoor Air Quality and model building codes. This new procedure makes use of the knowledge provided in Chapter 45 of the 2015 ASHRAE Handbook–Applications, and was tested against various physical modeling and full-scale studies.
The study demonstrated that the new method is more accurate than the existing Standard 62.1 equation which under-predicts and over-predicts observed dilution more frequently than the new method. In addition, the new method accounts for the following additional important variables: stack height, wind speed and hidden versus visible intakes. The new method also has theoretically justified procedures for addressing heated exhaust, louvered exhaust, capped heated exhaust and horizontal exhaust that is pointed away from the intake.
Included in the report are recommendations and documentation regarding minimum dilution factors for Class 1-4, wood burning kitchen, boiler, vehicle, emergency generator and cooling tower type exhaust.
Citation: ASHRAE Research
Product Details
- Published:
- 2016
- Number of Pages:
- 85
- Units of Measure:
- Dual
- File Size:
- 1 file , 3.5 MB
- Product Code(s):
- D-RP-1635