This paper summarizes an experimental and numerical study into a ventilation concept that combines displacement ventilation with task conditioning, the so-called desk displacement ventilation (DDV) concept. The study uses steady-state and transient results to discuss the applicability of the DDV concept for standard office room configurations. The evaluation of the concept focuses on the micro/macroclimate and thermal comfort. Results show that the separation between micro- and macroclimate, a characteristic of task conditioning, is less pronounced. Furthermore, the thermal comfort conditions at the desk limit the cooling capacity of a DDV system. Finally, the transient characteristics of the concept do not conform to stated requirements for task conditioning systems. The main conclusion, therefore, is that there is no particular advantage in sitting close to a displacement ventilation unit. An improvement of the DDV system is proposed by incorporating a parallel system that provides the fresh air near head level. The improvement of the combined system has been investigated using computational fluid dynamics.
Units: Dual
Citation: Symposium, ASHRAE Transactions, vol. 105, pt. 2, Seattle 1999
Product Details
- Published:
- 1999
- Number of Pages:
- 10
- File Size:
- 1 file , 2.1 MB
- Product Code(s):
- D-7506