1.1 This test method covers a spectroscopic procedure for determining the level of suspended water and particulate contamination (haze) in liquid middle distillate fuels including those blended with synthesized hydrocarbons or biofuels.
1.1.1 An ordinal, whole-number, Instrument Haze Rating (IHR) from 1 to 6 and a Haze Clarity Index (HCI) from 50.0 to 100.0 are determined on a test specimen at a temperature of 22.0 °C ± 2.0 °C.
1.1.1.1 The stated precision only applies at this temperature.
Product Details
- Published:
- 10/01/2017
- Number of Pages:
- 9
- File Size:
- 1 file , 220 KB