Yuma Proving Ground, Arizona, has successfully operated an external-melt ice-on-coil storage cooling system with nominal tank storage capacity of 1050 ton-h (3692 kWh) for the past 12 years. The system cools Building 506, which consists of two perpendicular, three-story wings with a total floor area of 86,100 ft2 (7999 m2). The ice storage system was a retrofitted “add-on†to the existing chilled water system and consists of one 220-ton (774 KW) centrifugal chiller and one 80-ton (281 KW) reciprocating chiller. The system’s design objective was to eliminate the electrical demand of the 220-ton (774 KW) chiller during the peak window of 1200-1600 hours. Yearly net savings of $22,450 in electrical utility costs paid back the construction cost of $144,969 in 6.5 years. This paper discusses system operation and maintenance and unanticipated benefits gained from operation in a changing deregulatory environment.
Units: Dual
Citation: Symposium Papers, Atlanta, GA, 2001
Product Details
- Published:
- 2001
- Number of Pages:
- 6
- File Size:
- 1 file , 230 KB
- Product Code(s):
- D-22527