This is the tenth article covering one of several energy-saving technologies evaluated in a recent U.S. Department of Energy report. The complete report is at www.eren.doe.gov/buildings/documents.
Microchannel heat exchangers (MCHXs) consist of flat microchannels connected in parallel between two headers with fan-fold fins brazed between adjacent tubes (Figure 1). Each microchannel tube is typically 0.05 in. to 0.1 in. (1 to 2.5 mm) thick and 0.5 in. to 1 in. (12 to 25 mm) wide and has multiple internal passages. The parallel flow arrangement enables use of MCHXs for largercapacity HVAC applications because it avoids the excessive pressure drop created by single-tube multi-pass designs. In fabrication, a manufacturer assembles the MCHX from its constituent
Citation: ASHRAE Journal, vol. 45 no. 12, December 2003
Product Details
- Published:
- 2003
- Number of Pages:
- 3
- File Size:
- 1 file , 660 KB
- Product Code(s):
- D-21002