The effects of retrofitting for building tightness, air-to-air heat exchangers, and HVAC circulation fans on radon and radon progeny levels were investigated using two matched test houses. One test house was retrofitted for tightness and outfitted with an air-to-air heat exchanger. The two houses were unoccupied; selected occupant-related activities were simulated in a controlled manner. Retrofit for tightness reduced the annual average air infiltration rate by 24% and increased radon and radon progeny concentrations by a similar amount. The air-to-air heat exchanger reduced radon and radon progeny concentrations commensurate with mechanical ventilation. Increased mixing from the furnace circulation fan equalized the upstairs/downstairs concentrations. Extended use of the circulation fan reduced radon progeny levels similar to those obtained with the heat exchanger (about 50% reduction). Seasons had considerable impact on indoor radon and radon progeny; higher levels were found in the summer and fall seasons.
Units: SI
Citation: Symposium, ASHRAE Transactions, 1985, vol. 91, pt. 2B, Honolulu, HI
Product Details
- Published:
- 1985
- Number of Pages:
- 9
- File Size:
- 1 file , 570 KB
- Product Code(s):
- D-HI-85-39-2