Click here to purchase
This paper investigated the energy saving potential of modulation control of hydronic fan-coil units (FCUs) relative to traditional on-off control. Building load profiles were first generated by using a hotel building model in EnergyPlus under five different climates. The typical performance of variable air variable water FCUs was represented by a group of empirical curves derived from experimental data. A system model consisting of multiple thermal zones served by FCUs, a variable speed pump, and a chiller was constructed by connecting the component models following the mass and energy balance approach. The simulation results showed that the modulation control could save 20-30% in FCU fan energy, 50-70% in pump energy, and 2-7% in total HVAC energy compared with the traditional on-off control.

Citation: 2019 Annual Conference, Kansas City, MO, Extended Abstracts

Product Details

Published:
2019
Number of Pages:
3
Units of Measure:
Dual
File Size:
1 file , 970 KB
Product Code(s):