Click here to purchase

This paper describes a study of the performance of a ventilation system in a typical patient room using CFD modeling and calculations of various ventilation indices. The results show that the use of basboard heating is necessary in extreme weather conditions. In particular, good occupant conditions are virtually impossible to achieve without baseboard heating. Further, in general weather conditions, a ventilation rate of 4 ACH provides adequate conditions, though an increase to 5 or 6 ACH is optimum.

Units: Dual

Citation: Symposium, ASHRAE Transactions, vol. 106, pt. 2

Product Details

Published:
2000
Number of Pages:
14
File Size:
1 file , 13 MB
Product Code(s):
D-7275