Click here to purchase

Product Details

Edition:
9
Published:
02/18/2022
Note:
This product is unavailable in Belarus, Russia, Ukraine

Click here to purchase
Please note: All interim revisions for this edition available at time of your purchase will be included.

1 Scope

1.1 These requirements cover the fire resistance performance of roof coverings exposed to simulated fire sources originating from outside a building on which the coverings are installed. They are applicable to roof coverings intended for installation on either combustible or noncombustible decks (see 1.7) when the roof coverings are applied as intended.

1.2 Three classes of fire exposure are described.

1.3 Class A roof coverings are effective against severe fire test exposures. Under such exposures, roof coverings of this class afford a high degree of fire protection to the roof deck, do not slip from position, and are not expected to produce flying brands.

1.4 Class B roof coverings are effective against moderate fire test exposures. Under such exposures, roof coverings of this class afford a moderate degree of fire protection to the roof deck, do not slip from position, and are not expected to produce flying brands.

1.5 Class C roof coverings are effective against light fire test exposures. Under such exposures, roof coverings of this class afford a light degree of fire protection to the roof deck, do not slip from position, and are not expected to produce flying brands.

1.6 Tests conducted in accordance with these requirements are intended to demonstrate the performance of roof coverings during the types and periods of fire exposure involved, but are not intended to determine the acceptability of roof coverings for use after exposure to fire. These fire test methods do not provide a basis to compare expected performance under all actual fire conditions but they do provide a basis for comparison of the response of roof coverings when subjected to fire sources that are described herein.

1.7 A combustible deck is formed of wood (sheathing boards or plywood). A noncombustible deck is formed of metal, concrete, or poured gypsum.

Product Details

Edition:
8th
Published:
04/22/2004
Number of Pages:
32